English French German Portuguese Spanish Russian Japanese Korean Arabic Irish Greek Turkish Italian Danish Romanian Indonesian Czech Afrikaans Swedish Polish Basque Catalan Esperanto Hindi Lao Albanian Amharic Armenian Azerbaijani Belarusian Bengali Bosnian Bulgarian Cebuano Chichewa Corsican Croatian Dutch Estonian Filipino Finnish Frisian Galician Georgian Gujarati Haitian Hausa Hawaiian Hebrew Hmong Hungarian Icelandic Igbo Javanese Kannada Kazakh Khmer Kurdish Kyrgyz Latin Latvian Lithuanian Luxembou.. Macedonian Malagasy Malay Malayalam Maltese Maori Marathi Mongolian Burmese Nepali Norwegian Pashto Persian Punjabi Serbian Sesotho Sinhala Slovak Slovenian Somali Samoan Scots Gaelic Shona Sindhi Sundanese Swahili Tajik Tamil Telugu Thai Ukrainian Urdu Uzbek Vietnamese Welsh Xhosa Yiddish Yoruba Zulu Kinyarwanda Tatar Oriya Turkmen Uyghur Abkhaz Acehnese Acholi Alur Assamese Awadish Aymara Balinese Bambara Bashkir Batak Karo Bataximau Longong Batak Toba Pemba Betawi Bhojpuri Bicol Breton Buryat Cantonese Chuvash Crimean Tatar Sewing Divi Dogra Doumbe Dzongkha Ewe Fijian Fula Ga Ganda (Luganda) Guarani Hakachin Hiligaynon Hunsrück Iloko Pampanga Kiga Kituba Konkani Kryo Kurdish (Sorani) Latgale Ligurian Limburgish Lingala Lombard Luo Maithili Makassar Malay (Jawi) Steppe Mari Meitei (Manipuri) Minan Mizo Ndebele (Southern) Nepali (Newari) Northern Sotho (Sepéti) Nuer Occitan Oromo Pangasinan Papiamento Punjabi (Shamuki) Quechua Romani Rundi Blood Sanskrit Seychellois Creole Shan Sicilian Silesian Swati Tetum Tigrinya Tsonga Tswana Twi (Akan) Yucatec Maya
inquiry
Inquiry
Form loading...
ZW32-12/630-20 12kV Intelligent Pole-Mounted Circuit Breaker
High Voltage Switchgear

ZW32-12/630-20 12kV Intelligent Pole-Mounted Circuit Breaker

High Voltage Series

Product Overview
Adopts a three-phase pillar-type vacuum arc-quenching structure. The solid-insulated pole integrates a vacuum interrupter, sensors, and power-taking components, supporting simultaneous collection of voltage/current signals on both inlet and outlet sides to provide power supply for intelligent feeder terminals.
● Operation Modes: Miniaturized spring operating mechanism is built into a sealed case, supporting manual, electric, and remote switching operations.
● Safety Design: External three-phase interlocking disconnector equipped with anti-misoperation interlocking device ensures operational safety.
● Integrated Design: Fully sealed insulated pole with IP68 protection class adapts to complex outdoor working conditions.
Note: Product parameters are subject to actual delivery.

    Features

    • product-description1
    • product-description2
    • product-description3

    Technical specifications

    No.

    Item

    Unit

    ZW32-12/T630-20

    ZW32-12/T630-20G

    1

    Arc extinguishing chamber type

    -

    Vacuum

    Vacuum

    2

    Insulating medium

    -

    Solid insulation

    Solid insulation

    3

    Rated voltage

    kV

    12

    12

    4

    Rated frequency

    Hz

    50

    50

    5

    Rated current

    A

    630

    630

    6

    Rated short-time withstand current

    kA

    20

    20

    7

    Rated short-circuit breaking current

    kA

    20

    20

    8

    Rated peak withstand current

    kA

    50

    50

    9

    Rated short-circuit duration

    s

    4

    4

    10

    Rated short-circuit breaking current breaking times

    Times

    ≥30

    ≥30

    11

    Rated operating sequence (ratings should not be reduced for rated operating cycles)

    -

    O-0.3s-CO-180s-CO

    O-0.3s-CO-180s-CO

    12

    Rated lightning impulse withstand voltage

    Phase-to-phase and phase-to-ground

    kV

    75

    75

    (1.2/50μs, peak value)

    Break

    kV

    85

    85

    13

    Rated power frequency short-time withstand voltage (1min)

    Phase-to-phase and phase-to-ground

    kV

    42

    42

    Break

    kV

    48

    48

    14

    Partial discharge of the whole machine (including current and voltage sensors and power supply module)

    Test voltage

    kV

    14.4

    14.4

    Partial discharge

    pC

    ≤20

    ≤20

    15

    Main circuit resistance

    μΩ

    ≤80

    ≤130

    16

    Mechanical stability

    Times

    ≥10000

    ≥10000

    17

    Actuating mechanism type

    -

    Spring

    Spring

    18

    Operation mode

    -

    Electric operation with manual opening/closing capabilities

    Electric operation with manual opening/closing capabilities

    19

    Operating voltage

    V

    DC24

    DC24

    20

    Switch closing time

    ms

    ≤60

    ≤60

    21

    Switch opening time

    ms

    ≤40

    ≤40

    22

    Opening and closing asynchronism

    ms

    ≤2

    ≤2

    23

    Current sensor encapsulated in the pole

    Rated current ratio

    Phase sequence

    600A/1V

    600A/1V

    Zero sequence

    20A/0.2V

    20A/0.2V

    Accuracy level

    Phase sequence

    Measurement Class 0.5s, Protection Class 5P10

    Measurement Class 0.5s, Protection Class 5P10

    Zero sequence

    Class 1, Protection Class 10P10

    Class 1, Protection Class 10P10

    Temperature range

    ℃

    -40℃~70℃

    -40℃~70℃

    Implementation method

    -

    Low-power electromagnetic type

    Low-power electromagnetic type

    24

    Voltage sensor encapsulated in the pole

    Rated voltage ratio

    Phase sequence

    (10kV/√3)/(3.25V/√3)

    (10kV/√3)/(3.25V/√3)

    Zero sequence

    (10kV/√3)/(6.5V/3)

    (10kV/√3)/(6.5V/3)

    Accuracy level

    Phase sequence

    Class 0.5

    Class 0.5

    Zero sequence

    Class 1

    Class 1

    Temperature range

    ℃

    -40℃~70℃

    -40℃~70℃

    Implementation method

    -

    Capacitive voltage division

    Capacitive voltage division

    Sampling method

    -

    Dual-side voltage acquisition (both source and load sides)

    Dual-side voltage acquisition (both source and load sides)

    25

    Capacitive Power-taking Power Supply Encapsulated in the Pole

    Power supply method

    -

    Built-in capacitive power supply

    Built-in capacitive power supply

    Installation method

    -

    Integrated capacitive power supply cast into the insulation pole

    Integrated capacitive power supply cast into the insulation pole

    Single-phase rated output power

    W

    ≥10±10%

    ≥10±10%

    26

    Remote and local lockout function  

    -

    Optional

    ≥10±10%

    27

    Recloser enable/disable function  

    -

    Optional

    ≥10±10%

    28

    Manual closing lockout  

    -

    N/A

    N/A

    29

    Switch enclosure protection level  

    -

    ≤IP67

    ≤IP67

    30

    Switch service life  

    Year

    20

    20

    Note: The above data is subject to change due to technical improvement.