01
HXGN-40.5 Gas-insulated Switchgear (GIS)
Features
● Safety & Reliability
The high-voltage components of this switchgear use low-pressure SF6 gas as the insulating medium, sealed in a stainless steel housing to isolate from the external environment. This effectively prevents contamination, moisture, foreign substances, and other harmful impacts, enhancing insulation reliability while offering excellent anti-aging and anti-corrosion properties.
● Compact Structure
Adopting mature vacuum switch technology with stable breaking performance and long service life, the arc extinguish chamber is horizontally arranged in the gas-filled housing. This fully leverages the excellent breaking capability of the vacuum interrupter, ensuring a compact structure, superior performance, and high reliability.
● Maintenance-Free
Using inner cone cable plug-in technology, cables, arresters, and PT can be connected via plug-in for stronger insulation. The gas box features a dual-chamber design: one chamber for the three-position switch and main busbar, and another for the circuit breaker unit, supporting one-key sequential control.
● Easy Installation
With solid insulated busbars, this gas-insulated switchgear eliminates on-site SF6 gas handling issues (e.g., vacuum pumping, gas filling, moisture treatment) during installation and operation expansion, enabling convenient field installation.
● Intelligent Configuration
Equipped with intelligent control and protection units, it monitors the operating status of circuit breakers, three-position disconnectors, energy-storage springs, and gas pressure in the gas-filled housing. It controls the opening/closing of circuit breakers and operation of three-position disconnectors, achieving relay protection automation.
Operating conditions
● Altitude: ≤2500m
● Ambient Temperature: -5°C to +40°C
● Relative Humidity: Daily average ≤85% (at +25°C)
● Seismic/Vibration: Installation site shall be free from severe vibration, jolts, and vertical inclination not exceeding 5 degrees.
● Environmental Hazards: No explosion risks
Note: For applications exceeding the above normal conditions, users shall consult with the manufacturer for customized solutions.
Technical specifications
|
No. |
Items |
Unit |
Data |
|
|
1 |
Rated voltage |
kV |
40.5 |
|
|
2 |
Maximum rated current |
A |
2000 |
|
|
3 |
Rated breaking current |
kA |
25 |
31.5 |
|
4 |
Rated closing current (peak value) |
kA |
63 |
80 |
|
5 |
Limiting through-current peak value |
kA |
63 |
80 |
|
6 |
Rated short-time withstand current (4s) |
kA |
25 |
21.5 |
|
7 |
Normal dimensions (W×D×H) |
mm |
1918×3250×3125 |
|
|
8 |
Protection level |
IP2X |
||
|
9 |
Weight |
KG |
About 1500 |
|