English French German Portuguese Spanish Russian Japanese Korean Arabic Irish Greek Turkish Italian Danish Romanian Indonesian Czech Afrikaans Swedish Polish Basque Catalan Esperanto Hindi Lao Albanian Amharic Armenian Azerbaijani Belarusian Bengali Bosnian Bulgarian Cebuano Chichewa Corsican Croatian Dutch Estonian Filipino Finnish Frisian Galician Georgian Gujarati Haitian Hausa Hawaiian Hebrew Hmong Hungarian Icelandic Igbo Javanese Kannada Kazakh Khmer Kurdish Kyrgyz Latin Latvian Lithuanian Luxembou.. Macedonian Malagasy Malay Malayalam Maltese Maori Marathi Mongolian Burmese Nepali Norwegian Pashto Persian Punjabi Serbian Sesotho Sinhala Slovak Slovenian Somali Samoan Scots Gaelic Shona Sindhi Sundanese Swahili Tajik Tamil Telugu Thai Ukrainian Urdu Uzbek Vietnamese Welsh Xhosa Yiddish Yoruba Zulu Kinyarwanda Tatar Oriya Turkmen Uyghur Abkhaz Acehnese Acholi Alur Assamese Awadish Aymara Balinese Bambara Bashkir Batak Karo Bataximau Longong Batak Toba Pemba Betawi Bhojpuri Bicol Breton Buryat Cantonese Chuvash Crimean Tatar Sewing Divi Dogra Doumbe Dzongkha Ewe Fijian Fula Ga Ganda (Luganda) Guarani Hakachin Hiligaynon Hunsrück Iloko Pampanga Kiga Kituba Konkani Kryo Kurdish (Sorani) Latgale Ligurian Limburgish Lingala Lombard Luo Maithili Makassar Malay (Jawi) Steppe Mari Meitei (Manipuri) Minan Mizo Ndebele (Southern) Nepali (Newari) Northern Sotho (Sepéti) Nuer Occitan Oromo Pangasinan Papiamento Punjabi (Shamuki) Quechua Romani Rundi Blood Sanskrit Seychellois Creole Shan Sicilian Silesian Swati Tetum Tigrinya Tsonga Tswana Twi (Akan) Yucatec Maya
inquiry
Inquiry
Form loading...
China Mobile Substation of American Type Outdoor Combined Substation Compact Pad Mounted Transformer Substation
Transformer Substation

China Mobile Substation of American Type Outdoor Combined Substation Compact Pad Mounted Transformer Substation

ZGS Series

Product Overview
This product is specifically designed for 7.2/12kV ring network, dual power supply, and terminal power supply systems, integrating high-voltage power distribution, metering, compensation, and protection functions. The high-voltage side is equipped with multi-position load switches and fuses, while the low-voltage side can be equipped with customized power distribution modules such as control devices, reactive power compensation, and energy metering as needed. The equipment supports indoor and outdoor installation and is widely used in industrial parks, commercial centers, high-rise buildings, and other similar settings.

    Model Definition

    product-description1-12

    Features

    ● Compact Design: Volume is only ~1/3 of domestic European-style substations with the same capacity.
    ● Fully Sealed & Insulated: Eliminates the need for insulation clearances, ensuring personal safety.
    ● Flexible Application: Suitable for both ring main and terminal systems with easy conversion, enhancing power supply reliability.
    ● Load-bearing cable joint: Rated load current can reach 200A. It can not only operate under normal load, but also act as a load switch in emergency conditions, and has a reliable isolating switch function.
    ●  It adopts a delta/star connection + column structure, which features excellent voltage quality, no neutral point offset, low cabinet temperature rise, low noise, and reliable lightning protection performance.
    • product-description2
    • product-description3
    • product-description4

    Operating conditions

    ● Altitude: ≤1000m (special design required for higher altitudes)
    ● Wind Pressure: ≤10Pa (equivalent to 35m/s)
    ● Humidity: Daily avg. ≤95%, monthly avg. ≤90%
    ● Temperature: -25°C to +40°C
    ● Vibration Resistance: Horizontal acceleration 0.4m/s²; vertical acceleration 0.15m/s²
    ● Seismic Intensity: 8 degrees
    ● Installation Inclination: ≤3°
    ● Environmental Requirements: Free from corrosive/flammable gases, water vapor pollution; no severe vibration at installation site.

    Technical specifications

    No.

    Items

    Unit

    Data

    1

    Rated voltage

    kV

    10/0.4 (HV/LV)

    2

    Maximum operating voltage

    kV

    12 (HV)

    3

    Rated frequency

    Hz

    50

    4

    Rated capacity

    kVA

    50-1600

    5

    1 min power frequency withstand voltage

    kV

    35

    6

    Lightning impulse withstand voltage

    kV

    50

    7

    Cooling method

    ONAN

    8

    High voltage backup fuse breaking current

    kA

    50

    9

    Plug-in fuse breaking current

    kA

    25

    10

    Ambient temperature

    ℃

    -35~+40

    11

    Allowable temperature rise of coil

    ℃

    65

    12

    No-load voltage regulation

    ±5% or ±2×2.5%

    13

    Noise level

    dB

    50

    14

    Protection level

    IP43

    Note: The above data is subject to change due to technical improvement.